Everyday Hazmat User’s Training Guide
Long Description
This image illustrates the floor plan to be used when storing corrosive products indoors and describes the requirements to be used for storage. These requirements are described as follows:
- No more than four control areas per structure.
- Each control area is separated
from other areas by a 1-hour firewall.
- No more than 5,000 pounds of solid and 500 gallons of liquid corrosive products can be stored in a control area. The amount can be increased by 100 percent if proper cabinets are used, and by another 100 percent if the area has sprinklers—not to exceed 300 percent of the original volume with both cabinets and sprinklers.