This image illustrates the floor plan to be used when storing class I and II oxidizers indoors and describes the requirements to be used for storage. These requirements are described as follows:
- No more than four control areas per structure.
- Each control area is separated
from other areas by a 1-hour firewall.
- No more than 4,000 pounds of class I or 250 pounds of class II liquid or solid oxidizers can be stored in a control area. The amount can be increased by 100 percent if proper cabinets are used, and by another 100 percent if the area has sprinklers�not to exceed 300 percent of the original volume with both cabinets and sprinklers.